Power for the HS-NCM for use with UL 9th Edition panels is provided via the NUP connection on the FACP itself or an external UL/ULC listed power supply. Power for the HS-NCM for use with UL 8th Edition panels must be provided by a 24 VDC UL/ULC listed power supply. Table 1 Voltage and Current Ratings for Communication Circuits NOTE: For use with the NFS-640, NFS2-640, NFS-320, NFS-3030, NFS2-3030, DVC-EM, NCA-2, and NCA, the HS-NCM must be connected via the NUP Ports! 2 The Network Communications Module for Wire (HS-NCM-W).
Figure 2 HS-NCM-SF/MF/MFSF. Enables software and database upload/download over High-Speed Noti.Fire.Net. NOTE: When referring to fiber-optic cables, the term “MF” indicates a multi-mode fiber and the term “SF” indicates a single-mode fiber. HS-NCM Installation Document — P/N 54014:B2. Port A and Port B assignment for the wire and fiber connections are set through VeriFire Tools.
Refer to the VeriFire™ Tools CD on-line help file. NOTE: When referring to fiber-optic cables, the term “MF” indicates a multi-mode fiber and the term “SF” indicates a single-mode fiber.
HS-NCM Installation Document — P/N 54014:B2. “Network Node Session” of the VeriFire Tools Upload/Download screen is shown as “Local VeriFire” Double click the node to log in to the panel. Using the mouse, right click on the node connected to the HS-NCM being configured. A menu of available options is displayed. HS-NCM Installation Document — P/N 54014:B2. Select “HS-NCM Parameters”.
The HS-NCM Parameters screen will be displayed listing HS-NCM defaults. HS-NCM Installation Document — P/N 54014:B2.
Once connected to an FACP, the HS-NCM will evaluate the network programming of the fire panel and set it’s node address accordingly. When power is applied to the HS-NCM without connection via the NUP port to an FACP, the HS-NCM will automatically configure itself as a repeater and it’s node address will be defaulted to zero. 6.1 Mounting Options The HS-NCM is designed to mount in a variety of CAB-3/CAB-4 compatible chassis, in the NFS-320 enclosure, on a BMP-1 blank plate for dress panel mounting, or behind the DVC-EM in the CA-1 or CA-2 audio chassis. HS-NCM-W can be door-mounted.
6.2 Interconnecting the HS-NCM-W When wiring consecutive HS-NCM-W boards, note that wiring may enter or exit at Port A or Port B as shown in Figure 7. HS-NCM-W port-to-port wiring is polarity sensitive. Port A must be connected to Port B of the next HS-NCM-W. A HS- NCM-W may be connected to any of the following devices:. – + – + – + Note: Wiring from the HS-NCM-W that is installed outside the building:. Cannot exceed 1000m (3280 ft.). Must be in conduit and is to be buried in a trench separate from any power lines.
Table 3 NOTI.FIRE.NET™ Connections: HS-NCM-MF/SF/MFSF 6.4 Mixing Wire & Fiber on One Network In some networks, it may be necessary to mix twisted-pair wire and fiber-optic cable—use a HS-NCM-WMF or HS- NCM-WSF as an interface between wire and fiber. Fiber ports are not polarity sensitive. However, port-to-port wiring for the HS-NCM wire connections are polarity sensitive. 6.5 Approved Cables and Distances for HS-NCM Applications The following table shows approved wiring cables that can be used with the HS-NCM and the maximum total distance allowed for each. Wire Type / Gauge Maximum Distance: Wire Type / Guage.
7 Diagnostic Indicators The HS-NCM has LEDs that serve as diagnostic indicators to help in troubleshooting and system connection. Refer to Table 5 for a list of diagnostic indicators and their descriptions. Refer to Figure 11 for diagnostic indicator locations. NFN wiring integrity and Port Mode mismatch. Refer to page 7 for Port Mode settings. ACTIVE Program Status Green Blinks On when a program on the HS-NCM is operating normally. PROGRAM Flash Programming Yellow Blinks On during Flash programming.
DO NOT REMOVE. 8 Supplemental Documentation The table below provides a list of document sources (manuals) containing additional information regarding the HS-NCM-W/MF/SF and the High-Speed Noti.Fire.Net products that it can connect to.
For information on Refer to Part No. Fire Alarm Control Panels High-Speed Noti.Fire.Net Manual.
. Fire Alarm Control Panel NFS2-3030/E Installation Manual Document 52544 Rev: P/N 52544:N1 ECN 13-0838. Adequate written records of all inspections (especially in bedrooms), smoking in bed, and violent explosions should be kept. Limit-D-1-2013 NFS2-3030/E Installation Manual — P/N 52544:N1. HARSH™, NIS™, and NOTI.FIRE.NET™ are all trademarks; and Acclimate® Plus, FlashScan®, NION®, NOTIFIER®, ONYX®, ONYXWorks®, UniNet®, VeriFire®, and VIEW® are all registered trademarks of Honeywell International Inc. Echelon® is a registered trademark and LonWorks™ is a trademark of Echelon Corporation.Brief description of content you think should be improved or corrected.Your suggestion for how to correct/improve documentation Send email messages to: FireSystems.TechPubs@honeywell.com Please note this email address is for documentation feedback only. If you have any technical issues, please contact Technical Services.
NFS2-3030/E Installation Manual — P/N 52544:N1. 3.14: Installing Printers.38 3.14.1: Printer Installation Sequence.39 3.14.2: Configuring the Printer.40 3.15: Wiring a Signaling Line Circuit (SLC).41 3.15.1: SLC Overview.41 3.15.2: SLC Capacity.41 3.15.3: SLC Installation.42 3.16: Connecting a PC for Programming.42 NFS2-3030/E Installation Manual — P/N 52544:N1.
A.3: Notification Appliance Circuits.62 A.4: Wire Requirements.62 B.1: Standalone Application.64 B.2: Local Network Application.64 B.3: Automatic Alarm Signal Silence.64 B.4: Annunciator Applications.64 B.5: Releasing Devices.64 B.6: Canadian SLC Devices.64 NFS2-3030/E Installation Manual — P/N 52544:N1. Underwriters Laboratories of Canada (ULC). ULC-S527-99 Standard for Control Units for Fire Alarm Systems. ULC S524 Standard for the Installation of Fire Alarm Systems Other. EIA-485 and EIA-232 Serial Interface Standards NFS2-3030/E Installation Manual — P/N 52544:N1. The following products have not received UL 864 9th Edition certification and may only be used in retrofit applications.
Operation of the NFS2-3030/E with products not tested for UL 864 9th Edition has not been evaluated and may not comply with NFPA 72 and/or the latest edition of UL 864. XP6-C Supervised Control Module Installation Document I56-1805 XP6-MA Six Zone Interface Module Installation Document I56-1806 XP6-R Six Relay Control Module Installation Document I56-1804 FSA-8000 FAAST Intelligent Aspiration Sensing Technology Document I56-3903 Table 1.1 Related Documents (2 of 3) NFS2-3030/E Installation Manual — P/N 52544:N1. INFORMATION ABOUT PROCEDURES THAT COULD CAUSE PROGRAMMING ERRORS, RUNTIME ERRORS, OR EQUIPMENT DAMAGE. WARNING: SUMMARY IN BOLD INDICATES INFORMATION ABOUT PROCEDURES THAT COULD CAUSE IRREVERSIBLE DAMAGE TO THE CONTROL PANEL, IRREVERSIBLE LOSS OF PROGRAMMING DATA OR PERSONAL INJURY. NFS2-3030/E Installation Manual — P/N 52544:N1. Connections to easily mount from one to ten Signaling Line Circuit (SLC) loops.
Network operation. Uses Notifier’s VIEW® early warning fire detection and the FlashScan® or CLIP families of detectors and modules. Alarm, Trouble, Supervisory and Security relays. THIS PRODUCT HAS BEEN CERTIFIED TO COMPLY WITH THE REQUIREMENTS IN THE STANDARD FOR CONTROL UNITS AND ACCESSORIES FOR FIRE ALARM SYSTEMS, UL 864 9TH EDITION. OPERATION OF THE NFS2-3030/E WITH PRODUCTS NOT TESTED FOR UL 864 9TH EDITION HAS NOT BEEN EVALUATED AND MAY NOT COMPLY WITH NFPA 72 AND/OR THE LATEST EDITION OF UL 864. Annunciators The NFS2-3030 supports ACM-24AT/ACM-48A (and their expanders) with either 64 or 96 points at an address, as well as ACM-16AT/ACM-32A/LDM-32 (and their expanders) with 64 points at an address and Notifier’s other ACS devices. (See Section 2.5 “Compatible Equipment” if looking for specific ACS devices.).
Power Sources and Outputs”) Note: Dotted line indicates location of optional keypad & LCD display.Circuits marked with an asterisk are supervised by communication loss. See Appendix A, “Electrical Specifications” for details. Figure 2.1 CPU Connections NFS2-3030/E Installation Manual — P/N 52544:N1.
See Section 3.10, “Connecting Power Sources and Outputs”, on page 33 for basic wiring connections; see the AMPS-24/E Manual for complete details. Refer to the AMPS-24/E Manual to determine whether your system requires an auxiliary power supply. NFS2-3030/E Installation Manual — P/N 52544:N1. TM-4 or NCM/HS-NCM. For information on audio chassis and dress panels, refer to the DVC Digital Voice Command Manual. NFS2-3030/E Installation Manual — P/N 52544:N1.
System Overview 2.5 Compatible Equipment Compatible Notifier and System Sensor equipment that connects directly to the CPU is listed below. These are the most common devices at time of publishing; the most complete list of compatible intelligent SLC loop devices is provided in the SLC Wiring Manual; for conventional non-addressable equipment see the Device Compatibility Document. EOLR-1 End of Line Resistor Assembly FSB-200 Single-ended beam smoke detector. Retrofit Equipment: Compatible Notifier Equipment Listed Under Previous Editions of UL 864 NOTE: The products in this list have not received UL 864 9th Edition certification and may only be used in retrofit applications (see Section 1.2, “UL 864 Compliance”, on page 8). Amplifiers Manual, DVC-RPU Manual, AA-series Audio Amplifiers Manual, DS-DB Manual Annunciators and other ACS devices Installation document for the specific device (such as ACS Manual, ACM-8R Manual, etc.) Table 3.1 Installation Checklist (1 of 2) NFS2-3030/E Installation Manual — P/N 52544:N1. Use the four holes in the back surface of the backbox to provide secure mounting (See Figure 3.1). Mount the backbox on a surface that is in a clean, dry, vibration-free area.
NFS2-3030/E Installation Manual — P/N 52544:N1. CAB-4 Series backbox, A-size (one-row) Keyholes 2 places Mounting holes 2 places Chassis- Chassis- mounting mounting studs studs (2 per row of (2 per row of backbox) backbox) Figure 3.1 Backbox-Mounting Holes and Chassis-Mounting Studs NFS2-3030/E Installation Manual — P/N 52544:N1. Figure 3.6. See Section 3.5.2, “Mounting in the CA-2 Audio System Chassis” and Half-chassis for the CA-2 Installation Document. DVC and optional NCM/HS-NCM. Figure 3.3 CA-2 Audio Chassis Assembly NFS2-3030/E Installation Manual — P/N 52544:N1. CPU2-3030D (with keypad/display) requires the longer stand-offs: 1.5 inch (38.1 mm); CPU2-3030ND (without keypad/display) requires the shorter stand-offs: 0.25 inch (6.35 mm) Slide circuit-board tabs into slots on chassis as shown in Figure 3.5.
NFS2-3030/E Installation Manual — P/N 52544:N1. (DVC). a microphone and telephone handset well.
a microphone Figure 3.6 CA-2 Chassis Assembly CA-2 can also mount TELH-1, an optional telephone handset. NFS2-3030/E Installation Manual — P/N 52544:N1. This battery’s shelf-life should exceed 10 years, but if for some reason it fails, the control panel will show a trouble when powered up. To replace the lithium battery: Make a full backup of all system settings to prevent loss of all programming data. Disconnect all power sources. NFS2-3030/E Installation Manual — P/N 52544:N1.
CHS-M3 to the right of the CPU; additional modules can be mounted in other chassis. There are no slots in the first (back) two layers, but option boards with tabs (such as NCM-W) will still fit in those positions. NFS2-3030/E Installation Manual — P/N 52544:N1. Control and Expander Modules”.
NOTE: Mounting two pairs of loop-control and -expander modules in one chassis position may cause intermittent electrical interference. If this occurs, move one pair to a separate chassis position. NFS2-3030/E Installation Manual — P/N 52544:N1. CHS-4L see Figure 3.14. NOTE: Mounting two pairs of loop control and expander modules in one chassis position may cause intermittent electrical interference. If this occurs, move one pair to a separate chassis position. NFS2-3030/E Installation Manual — P/N 52544:N1.
LEM-320 mounted to it will be set to loop number 6. 3.8.4 Enabling External Power Supervision With LCM-320 revision 2.0 and higher, some type codes have external power supervision built into the software; see Section 4.2 “Devices Requiring External Power Supervision” for details. NFS2-3030/E Installation Manual — P/N 52544:N1. J2 LEM-320 Connection LCM-320 Connection SW1 Set to assign a unique SLC loop number LCM-320 LEM-320 Note: Do not cut any jumpers on the LCM-320 or LEM-320. Figure 3.11 LCM-320 and LEM-320 Diagram NFS2-3030/E Installation Manual — P/N 52544:N1.
NOTE: Depending on system components, clearance may be tight. Do not force modules! Move the assembly around gently until you find the angle where components and mounting studs pass each other without scraping together.
NFS2-3030/E Installation Manual — P/N 52544:N1. Figure 3.15 Connecting Multiple Pairs of Loop Control and Expander Modules Figure 3.15 Connecting Multiple Pairs of Loop Control and Expander Modules LCM-320 (in front) LEM-320 (in back) Figure 3.16 SLC Loop Connections on Loop-Control and Loop-Expander Modules NFS2-3030/E Installation Manual — P/N 52544:N1. Secondary power source. +24 VDC from batteries, installed in the control panel (or in an optional battery cabinet). Secondary (battery) power is required to support the system during loss of primary power. External power sources.
+24VDC auxiliary power supplies that are UL/ULC-listed for fire protective service. NFS2-3030/E Installation Manual — P/N 52544:N1. 3.10.3 Checking AC Power Table 3.2 contains a checklist for checking the system with AC power applied to the main power supply: CAUTION: WHILE CHECKING AC POWER, MAKE SURE BATTERIES ARE NOT CONNECTED. NFS2-3030/E Installation Manual — P/N 52544:N1.
NOTE: If additional knockouts are added to the backbox, proper separation of power-limited and non-power-limited Separating non-power-limited and wiring should be maintained. Power limited circuits within the backbox with adhesive squares Figure 3.19 Typical Wiring in a Four-Row Backbox NFS2-3030/E Installation Manual — P/N 52544:N1. NOTE: Relays are power-limited only when connected to power-limited sources for the relay outputs.
NFS2-3030/E Installation Manual — P/N 52544:N1. A HI B HI LED6 LED7 RCDA RCDB LED4 LED2 STATA STATB LED3 LED5 RECON PULSE1 LED1 LED8 RESET POWER TERM NCM-W NCA-2 Figure 3.20 Central Station Canadian Requirements for Second Dial-Out Connection NFS2-3030/E Installation Manual — P/N 52544:N1. The control panel can be configured to time-stamp the printout with the current time-of-day and date for each event.
The printer can be located up to 50 feet (15.25 m) from the control panel. Installation and configuration instructions follow. NFS2-3030/E Installation Manual — P/N 52544:N1. Configure the printer as described in Section 3.14.2 “Configuring the Printer”. NOTE: Depending on which version of the AMPS-24/E is being used, the terminal block designations may differ from those listed.
Please refer to the AMPS-24/E manual. NFS2-3030/E Installation Manual — P/N 52544:N1. Programming Manual for instructions.). Data bits: 8. Parity: None.
Stop bits: 1 Table 3.4 Keltron DIP Switch Settings Set the printer DIP switches SP1 and SP2 according to settings in Table 3.4. NFS2-3030/E Installation Manual — P/N 52544:N1. Loops must be programmed for Rapid Poll (refer to the programming manual for specific instructions).
Modules on a fully loaded loop must adhere to a ratio of two monitor modules to one control module. NFS2-3030/E Installation Manual — P/N 52544:N1. NOTE: Download operations that change the basic program of the control panel must be performed by responsible service personnel in attendance at the control panel. After downloading a program, test the control panel in accordance with NFPA 72. NFS2-3030/E Installation Manual — P/N 52544:N1. (Not required for contains wiring conversion FlashScan type codes charts for type V and type H modules. That provide built-in power supervision.) Figure 4.1 Enabling External Power Supervision Using Relays NFS2-3030/E Installation Manual — P/N 52544:N1.
NOTE: The following models do not comply with requirements for AC loss delay reporting when used with Central Station Protected Premises systems: AA-30, AA-120, AA-100, APS-6R, CHG-120. NOTE: For additional setup information for UDACT, refer to the UDACT Installation Manual. NFS2-3030/E Installation Manual — P/N 52544:N1. Uninterruptable Power Supply (UPS) 50 watt minimum, UL-listed for Fire Protective Signaling is recommended.
A UPS is required for NFPA 72 Proprietary Protected Premises Receiving Unit Applications. Figure 4.3 Typical Proprietary Fire Alarm Systems Wiring Connections: Block View NFS2-3030/E Installation Manual — P/N 52544:N1. Security Module I/O Circuit Shielding - terminate the shield at earth ground at the junction box containing the module. When employed as a Protected Premises Unit, the NFS2-3030 cabinet door must be wired with an STS-1 Tamper Switch that is monitored by the control panel.
NFS2-3030/E Installation Manual — P/N 52544:N1. Connect the STS-1 connector to J6 Security on the CPU. Program panel supervision for Tamper Input “Yes”. Connect to J6 Security STS-1 mounting location (side opposite of door hinges) Figure 4.5 Installing the STS-1 Security Tamper Switch NFS2-3030/E Installation Manual — P/N 52544:N1.
SLC manual appendix, which contains wiring conversion charts for type V and type H modules. UL-listed, normally-closed FMM-1 security switch Figure 4.6 Wiring Diagram for Proprietary Security Alarm Applications NFS2-3030/E Installation Manual — P/N 52544:N1. SLC manual appendix, which contains wiring conversion RKS-S rear charts for type V and type H modules. R-47K End-of-Line Resistor Figure 4.8 Connecting the FMM-1 Module to the RKS-S NFS2-3030/E Installation Manual — P/N 52544:N1. Programming Notes for Figure 4.9 Programming of Key Switch, Access Points, and Motion Detection RKS Remote Key Switch with Monitor Module Address: LXXMYYY (arbitrary) Type ID: ACCESS MONITOR Zone Map: (none) Custom Label: Arming Switch NFS2-3030/E Installation Manual — P/N 52544:N1. Type ID: RELAY Zone Map: Custom Label: Security Group Output Signal Silence: No Walk Test: Yes/No (Installer Specified) Switch Inhibit: Yes B. MM Programming Address: LXXMYYY (arbitrary) Type ID: SECURITY-L Zone Map: (none) NFS2-3030/E Installation Manual — P/N 52544:N1.
Power-limited wiring. Supervised for open circuit only. Supervised for open circuit and shorts.
Supervised for power loss. Supervised for power loss For more information, refer to the NFS2-3030 Programming Manual. NFS2-3030/E Installation Manual — P/N 52544:N1. End-of-Line device as shown in Figure 4.11. B) All wiring for releasing circuits is supervised against open and shorts. C) Program the releasing circuit for Type Code REL CKT ULC For applications not requiring power-limited circuits: NFS2-3030/E Installation Manual — P/N 52544:N1.
See figure 4.12. Refer to the SLC Manual for detailed wiring information. Monitor Module Mechanical Disconnect Switch listed for the application Note: Disconnect switch must provide separate dry contacts to indicate supervisory. Figure 4.12 Typical Connection of a Mechanical Disconnect Switch NFS2-3030/E Installation Manual — P/N 52544:N1.
Th8320u1008 Installation Manual
Do not loop wiring under the screw terminals. Break the wire run to provide supervision of connections. All applications using the FCM-1-REL are power-limited: Program the releasing circuit for Type Code REL CKT ULC or RELEASE CKT. NFS2-3030/E Installation Manual — P/N 52544:N1. NOTE: Devices for use in releasing applications must be programmed as type code RELEASE CIRCUIT or REL CKT ULC. 4.10 Connecting an FAAST Intelligent Aspiration Detector The FAAST Intelligent Aspiration detector may be used to provide early warning fire protection using aspiration sensing technology. NFS2-3030/E Installation Manual — P/N 52544:N1.
From Power Supply or Previous Device - For additional installation information for the FAAST detector, refer the FSA-8000 FAAST Installation and Maintenance Instruction document (I56-3903) and the SLC Wiring Manual Figure 4.15 FSA-8000A Connection to the FACP (51253). NFS2-3030/E Installation Manual — P/N 52544:N1. The minimum DC resistance between conductors of an unpopulated SLC pair cannot be less than 1 K ohms.
Measure DC resistance on an unpopulated loop as shown in Figure 5.1 on page 59. Continued NFS2-3030/E Installation Manual — P/N 52544:N1.
If Sulfuric Acid gets into eyes, seek immediate medical attention. Ensure proper handling of the battery to prevent short circuits. Take care to avoid accidental shorting of the leads from uninsulated work benches, tools, bracelets, rings, and coins. NFS2-3030/E Installation Manual — P/N 52544:N1. Testing the System Battery Checks and Maintenance CAUTION: SHORTING THE BATTERY LEADS CAN DAMAGE THE BATTERY, EQUIPMENT, AND COULD CAUSE INJURY TO PERSONNEL. NFS2-3030/E Installation Manual — P/N 52544:N1. Notes NFS2-3030/E Installation Manual — P/N 52544:N1.
NOTE: If running an SLC in conduit with Notification Appliance Circuits, you can reduce problems by exclusively using electronic sounders (such as the MA/SS-24 Series) instead of more electronically noisy notification appliances (such as electromechanical bells or horns). NFS2-3030/E Installation Manual — P/N 52544:N1. +24 VDC power to devices within the same enclosure as the CPU. If those devices have outputs, the outputs must be power-limited. Power rating is determined by the power source(s).
See Section 3.10.1 “Overview”, and the AMPS-24 Manual for more details. NFS2-3030/E Installation Manual — P/N 52544:N1. Supervision for shorts is required; use REL-47K and type code Rel Ckt ULC. Refer to Section 4.6 “Releasing Applications”.
B.6 Canadian SLC Devices For a complete list of ULC-listed SLC loop devices, see SLC Wiring Manual, Appendix C “Canadian Versions of SLC Devices”. NFS2-3030/E Installation Manual — P/N 52544:N1. Electrical Connections 33 tem 44 Electrical Specifications 62 NFPA 72 Remote Station Fire Alarm Sys- Enclosures, see Backboxes 16 tem 44 External Power Supervision 43 Overview 43 Protected Premises Unit 44 Non-Power-Limited Circuits NFS2-3030/E Installation Manual — P/N 52544:N1. Service 58 Signalling Line Circuit, also see SLC 41 SLC Loop Modules External Power Supervision 43 SLC Loop Number 29 SLC, also see SLC Wiring Manual Specifications 62 SLC, see SLC Wiring Manual NFS2-3030/E Installation Manual — P/N 52544:N1. Manufacturer's Return Material Authorization form.
The replacement part shall come from Manufacturer's stock and may be new or refurbished. THE FOREGOING IS DISTRIBUTOR'S SOLE AND EXCLUSIVE REMEDY IN THE EVENT OF A WARRANTY CLAIM. Warn-HL-08-2009.fm NFS2-3030/E Installation Manual — P/N 52544:N1. World Headquarters 12 Clintonville Road Northford, CT USA 203-484-7161 fax 203-484-7118 www.notifier.com.